Fire Guard F-60 Exam Prep: Free F60 Practice Test

Think you can ace the G60 practice exam? Get started now!

Difficulty: Moderate
2-5mins
Learning OutcomesCheat Sheet
Paper art illustration for F60 practice test quiz on a coral background

This F-60 practice test helps you prepare for the Fire Guard F-60 exam with realistic questions, clear answers, and instant feedback. Use it to spot gaps before the exam and build confidence; when you're done, get more practice with our companion quiz.

Which of the following best describes the primary purpose of a licensed Fire Guard?
To conduct fire drills
To maintain and operate fire safety systems
To prevent fires and ensure occupant safety
To extinguish all fires
Fire Guards are licensed to prevent fires and ensure occupant safety within buildings. They conduct regular patrols to inspect fire protection equipment and identify hazards. They respond to alarms and enforce safe conditions to minimize risk. For more details, see .
How often must a Fire Guard renew their certificate in NYC?
Every 2 years
Every 3 years
Every 1 year
Every 5 years
The FDNY requires Fire Guards to renew their certificate every three years to ensure ongoing knowledge of current codes. Renewal involves submitting proof of completed continuing education and application fees. Timely renewal helps maintain compliance with safety regulations. See for more information.
Which of the following tasks is NOT an authorized responsibility of a Fire Guard?
Use portable fire extinguishers
Operate a standpipe system
Investigate fire alarms
Conduct fire safety patrols
Fire Guards are not permitted to operate standpipe systems - only qualified Fire Department personnel may do so. Fire Guards do investigate alarms, use fire extinguishers, and carry out safety patrols as part of their duties. Operating complex fixed systems requires additional certification. For details, see .
When a fire alarm is activated in a building under their watch, a Fire Guard must first:
Ignore the alarm if it seems false
Investigate the cause of the alarm
Evacuate the entire building immediately
Call the fire department before anything else
The first duty of a Fire Guard when an alarm sounds is to investigate and determine the cause. They must inspect the alarm zone to confirm if it is a real fire or a false activation. Only after assessing the situation should they call the fire department or initiate evacuation. More guidance is available in .
Where should Fire Guards display their certificate while on duty?
In a locked office
Inside the main fire alarm panel room
On their person at all times
In the building lobby
Fire Guards must carry their certificate on their person to present it upon request by authorities or building management. This ensures immediate proof of qualification while on patrol. Displaying it elsewhere may delay verification. For official posting and carrying requirements, see .
What is the minimum age requirement to apply for an NYC Fire Guard certificate?
21 years old
18 years old
16 years old
25 years old
Applicants must be at least 18 years old to qualify for a Fire Guard certificate in New York City. This age requirement ensures legal adulthood and responsibility. Applicants also must pass an approved training course. See application details at .
Which of the following operations always requires a Fire Guard to be on-site?
Hot work operations like welding
Painting interior walls
Routine office cleaning
Carpet installation
Hot work activities such as welding or cutting produce sparks and heat that can ignite nearby combustibles. Fire Guards are mandated to be present during such operations to conduct fire watches and respond quickly. They monitor the area before, during, and after the work. For standards, see .
After completion of hot work, how long must a Fire Guard maintain a fire watch?
120 minutes
30 minutes
60 minutes
10 minutes
A 30-minute post-hot work fire watch is required to detect smoldering fires that may ignite later. The guard should monitor the work area continuously during this period. This requirement is specified in NFPA 51B and adopted by NYC. For full guidance, see .
Which class of flammable liquid has a flashpoint below 73°F and a boiling point below 100°F?
Class IA
Class II
Class IB
Class IC
NFPA 30 defines Class IA liquids as those with flashpoints below 73°F and boiling points below 100°F. These liquids present high fire hazards due to low ignition temperatures. Proper classification ensures correct storage and handling. For details, see .
According to the NYC Fire Code, what minimum distance must aboveground storage tanks of Class I flammable liquids be from building lines?
25 feet
10 feet
75 feet
50 feet
NYC Fire Code Chapter 27 requires Class I liquid tanks to be at least 50 feet from building lines to minimize exposure. This separation reduces risk of fire spreading to structures. Site plans must reflect this distance. See for specifics.
During a fire watch for an impaired system, patrol inspections must occur at least every:
30 minutes
120 minutes
60 minutes
15 minutes
The FDNY mandates patrols at least every 30 minutes during any impairment of fire protection systems. Frequent inspections ensure hazards are identified and addressed promptly. Patrols must be logged and retained for review. More in .
Which fire extinguisher type is suitable for Class C fires?
Carbon dioxide (CO2)
Wet chemical
Water
Foam
CO2 extinguishers are recommended for energized electrical (Class C) fires because they leave no residue and do not conduct electricity. They work by displacing oxygen around the fire. Using water on electrical fires is dangerous. For more, visit .
What is the maximum allowed travel distance to a portable fire extinguisher, per NYC Fire Code?
75 feet
100 feet
150 feet
50 feet
NYC Fire Code stipulates a maximum of 75 feet travel distance to an extinguisher for most occupancy hazards. This ensures quick access in case of fire. Distances vary by hazard classification, but 75 feet is common. Details are in .
If an automatic sprinkler system malfunctions, a Fire Guard must:
Assist occupants with load management
Operate the sprinkler pump manually
Conduct manual patrols and notify FDNY
Ignore the issue until repair
When sprinklers fail, Fire Guards conduct frequent manual patrols and immediately notify the FDNY to maintain safety. Automatic and manual systems must be monitored until repairs are complete. They must log each inspection. See for details.
Which log entry is NOT required in the Fire Guard's patrol log?
Observed hazards
Details of system impairments
Time of each patrol
Personal hours worked
Fire Guard logs must record patrol times, observed hazards, and system impairments, but not the guard's personal hours. Logs are maintained to track fire safety conditions. Personal timekeeping is handled separately by employers. Further guidance is at .
When an automatic fire alarm system is impaired, Fire Guards must be stationed at each required exit for:
Only during business hours
30 minutes
60 minutes
Until the system is restored
Fire Guards remain at exits for the entire duration of the impairment to ensure safe egress. They are relieved only when the system is fully operational again. This continuous coverage is mandated by FDNY rules. See .
What minimum clearance must be maintained between stored materials and the nearest sprinkler deflector?
6 inches
18 inches
36 inches
24 inches
NFPA 13 requires an 18-inch clearance beneath sprinkler deflectors to allow proper water distribution. This clearance prevents storage from blocking spray patterns. Fire Guards verify this spacing during inspections. More at .
Which NFPA standard contains requirements for the inspection and testing of fire pumps?
NFPA 10
NFPA 25
NFPA 72
NFPA 14
NFPA 25 is the accepted standard for inspection, testing, and maintenance of water-based fire protection systems, including fire pumps. Fire Guards should be familiar with these requirements during system impairments. This standard helps ensure reliability. For full text, visit .
According to NYC Fire Code, the maximum travel distance to reach a standpipe hose connection in high-rise buildings is:
150 feet
130 feet
75 feet
100 feet
High-rise buildings must have standpipe hose connections accessible within 130 feet of any point on a floor. This requirement ensures adequate reach of hoselines. Fire Guards verify signage and accessibility. See for details.
Which class of flammable liquids has a flashpoint at or above 100°F and below 140°F?
Class IC
Class IA
Class II
Class IB
NFPA 30 designates liquids with flashpoints from 100°F to below 140°F as Class II. These liquids require specific storage and handling to prevent ignition. Fire Guards identify and label these containers correctly. Full definitions are in .
Fire Guard logs must be retained on site for a minimum of:
1 year
6 months
3 years
5 years
The FDNY requires that all Fire Guard logs and records be kept on site for at least three years for audit and compliance verification. Retention ensures a documented history of patrols and incidents. Older records may be archived according to building policy. See .
Which of the following is NOT considered fire safety equipment that Fire Guards are responsible for monitoring?
Fire alarms
Fire extinguishers
Sprinkler systems
Elevators
Elevators are maintained and inspected by building engineers, not Fire Guards. Fire Guards focus on active fire protection equipment like sprinklers, extinguishers, and alarms. They inspect these systems during patrols. For scope of duties, see .
Before applying for a Fire Guard certificate, an applicant must complete how many hours of FDNY-approved training?
4 hours
8 hours
16 hours
24 hours
Prospective Fire Guards must complete an eight-hour FDNY-approved fire watch course covering code requirements and duties. This training equips them to handle emergencies and perform patrols. Course completion proof is required with the application. Details at .
Which section of the NYC Fire Code specifically outlines requirements for conducting a fire watch during hot work operations?
57-03
57-02
57-04
57-01
NYC Fire Code Section 57-03 details the procedures for fire watches during hot work, including patrol frequency, equipment, and duration. It sets specific criteria for Fire Guards to monitor welding, cutting, and other heat-producing operations. Familiarity with this section is crucial for compliance. See for full requirements.
Upon impairment of an automatic sprinkler system, the building owner must notify the FDNY within:
24 hours
2 hours
30 minutes
6 hours
The NYC Fire Code requires building owners or agents to notify the FDNY within two hours of sprinkler system impairment. This prompt notification ensures rapid deployment of Fire Guards and corrective action. Failure to comply may result in penalties. For notification protocols, see .
0
{"name":"Which of the following best describes the primary purpose of a licensed Fire Guard?", "url":"https://www.quiz-maker.com/QPREVIEW","txt":"Which of the following best describes the primary purpose of a licensed Fire Guard?, How often must a Fire Guard renew their certificate in NYC?, Which of the following tasks is NOT an authorized responsibility of a Fire Guard?","img":"https://www.quiz-maker.com/3012/images/ogquiz.png"}

Study Outcomes

  1. Understand Exam Structure -

    Learn the F-60 exam format, including question types, time limits, and scoring criteria to navigate the test with confidence.

  2. Apply Effective Test Strategies -

    Discover proven techniques for tackling multiple-choice and scenario-based questions on the f60 practice test to maximize accuracy.

  3. Identify Key Fire Guard Concepts -

    Pinpoint essential fire prevention principles and safety protocols featured in the FDNY G60 practice test for focused study.

  4. Evaluate Your Performance -

    Use instant feedback and answer explanations to assess strengths and weaknesses, enabling targeted review before exam day.

  5. Build Exam Confidence -

    Simulate the real f-60 exam environment, track your progress, and reinforce knowledge to approach the test with assurance.

Cheat Sheet

  1. Fire Dynamics & Flashover Basics -

    Master fire behavior essentials, focusing on flashover - commonly tested on the f60 practice test - at about 500°C. Remember "Flash Over Five Hundred" for the threshold and use Q̇ = m·ΔHc from NFPA fire dynamics literature to calculate heat release (source: NFPA Journal).

  2. NYC Fire Code & Regulations -

    Review Title 29 of the NYC Admin Code and FDNY's official materials to align with FDNY G60 practice test content. Emphasize code requirements for F-60 certificate holders, permitting procedures, and compliance checkpoints (source: FDNY official website).

  3. Fire Guard Duties & Logkeeping -

    Learn to conduct patrols every 30 minutes and document findings in a clear log format - an area frequently covered in g60 practice exam questions. Note time, location, and condition in each entry to match the structure expected in f-60 exam questions and answers (source: FDNY Fire Guard Manual).

  4. Fire Protection Systems & PASS Method -

    Identify extinguisher classes (ABC, CO₂, K) and apply the PASS method - Pull, Aim, Squeeze, Sweep - highlighted in many f-60 exam questions. Practice matching equipment specs to scenario-based questions drawn from NFPA 10 and official training guides.

  5. Emergency Response & Evacuation Procedures -

    Plan evacuation routes, muster points, and communication steps using the FADEP mnemonic (Find Alarm, Attack, Delay, Evacuate, Protect) found in g60 practice test materials. This framework aligns with FEMA Emergency Response guidelines often referenced in f-60 practice test prep.