Plumbing Test
To prevent the entry of rodents into the building, strainer plates on drain inlets shall be be installed so that the openings are not greater than ____ inches in the least diameter.
1/2"
1/4"
3/8"
5/8"
A pipe sleeve used for pipe protection shall be ____ greater than the size of the pipe passing through the wall.
1 pipe size
1 inch
2 pipe sizes
2 inches
Water service piping shall be installed not less than ____ below the finished grade.
12"
18"
24"
30"
When trenches are over excavated, backfilling shall be placed in layers of ____ inches maximum depth.
2"
4"
6"
8"
Protective shield plates shall extend a maximum of ____ inches above the sole plate and below the top plate.
2"
4"
6"
8"
When rock is encountered in trenching, it shall be removed to a maximum of ____ inches below the bottom of the pipe.
2"
3"
4"
6"
When cast iron pipe in 10-foot is used, the maximum horizontal spacing of hangers is ____ feet.
5'
10'
15'
20'
Water supply systems may be tested with an air test of not less than ____ psi.
40 psi
80 psi
100 psi
160 psi
Rigid support sway bracing for plastic pipe shall be provided at changes in direction greater than 45 degrees for pipe size ____ inches and larger.
4"
6"
8"
10"
Air tests for the DWV system are conducted with a pressure of ____ psi.
5 psi
10 psi
20 psi
50 psi
Water closets shall not be closer than ____ inches from the centerline to any sidewall.
12"
15"
18"
21"
Separate employee facilities shall not be required in occupancies in which ____ or less people are employed.
14
16
20
25
In office buildings, bathroom and toilet rooms, urinals shall not be substituted for more than ____ percent of the required water closets.
25%
50%
67%
75%
The path of travel to the required facilities for an employee in a covered mall shall not exceed ____ feet.
200'
250'
300'
500'
Shower valves shall be equipped with a means to limit the maximum setting to ____ degrees Fahrenheit.
110 degrees F
120 degrees F
130 degrees F
140 degrees F
Bathtubs shall have waste outlets at least 2" in diameter.
True
False
The water supply to flush tanks equipped for automatic flushing shall be controlled with a timing device or sensor control device.
True
False
Fixtures for dormitories are based on one water closet per eight male or female students.
True
False
Trough urinals are permitted where approved by the Code Official.
True
False
The outlet of a pressure temperature or other relief valve may be directly connected to the drainage system.
True
False
Water heaters than contain a potential source of ignition must be elevated at least ____ inches in garages.
18"
24"
30"
36"
Bottom fed water heaters shall have a vacuum relief valve installed.
True
False
A water heater used as part of a space heating system shall have a maximum outlet water temperature of ____ degrees.
120 degrees
140 degrees
160 degrees
175 degrees
Water heaters installed in crawl spaces shall be supported on a solid base at least ____ inches thick.
2" thick
3" thick
4" thick
5" thick
Relief valves shall discharge piping shall be piped within ____ of the floor.
2"
4"
6"
8"
The cold water line valve shall be installed on the same floor and within ____ of the water heater served.
2'
3'
4'
5'
The maximum travel distance to an attic water heater from the access opening to the water heater is ____ feet.
10'
20'
45'
50'
Drain pan drain lines extended to the exterior of the building are allowed to terminate at a maximum height of ____ inches.
6"
12"
18"
24"
The minimum dimension of the required access opening into a crawl space for servicing and replacing water heaters is ____ x ____.
22" x 30"
24" x 30"
26" x 30"
30" x 30"
Where water pressure within a building exceeds ____ psi static, an approved water pressure reducing valve with a strainer shall be installed to reduce the pressure to ____ psi static.
80psi / 80psi
45psi / 45psi
60psi / 60psi
50psi / 50psi
The required capacity of residential sinks is ____ gallons per minute.
1.5 gpm
1.75 gpm
3.5 gpm
1 dfu
A device designed and installed to separate and retain for removal, by automatic or manual means, deleterious, hazardous, or undesirable matter from normal wastes, while permitting normal sewage or wastes to discharge into the drainage system by gravity.
Food and waste grinder
Solid interceptor
Oil separator
Interceptor
Water service pipe and the building sewer shall be separated by ____ feet of undisturbed or compacted soil when the sewer pipe does not conform to Table 702.2.
2 feet
5 feet
10 feet
None of the above
Additions, alterations, or repairs shall not cause an existing system to become ____, unsanitary or overloaded.
Obsolete
Non-compliant
Unsafe
Illegal
Water heaters and storage tanks shall be located and connected so as to provide ____ for observation, maintenance, servicing and replacement.
Access
Clearance
Space
Direct access
Facilities that are required for employees shall have a maximum travel distance of ____ from the employee’s regular working area.
100 feet
250 feet
400 feet
500 feet
Where separate systems of sanitary drainage and storm drainage are installed in the same property, the sanitary and the storm building sewers or drains shall be ____ to be laid side by side in one trench.
Prohibited
Permitted
Allowed
Not allowed
Hot water distribution pipe and tubing shall have a minimum pressure rating of ____ psi at 180*F.
85 psi
100 psi
140 psi
160 psi
In each bathroom or toilet room not used for assembly or educational purposes, urinals shall not be substituted for more than ____ percent of the required water closets.
25%
50%
67%
75%
For water service piping cement or concrete joints shall be ____.
ASME 1124.46 rated
Pressure tested to 160 psi
Properly aligned before grouting
Prohibited
Any pipe that passes within ____ under a footing or through a foundation wall shall be provided with a relieving arch or pipe built into the foundation wall.
6"
12"
18"
24"
Piping within a public or private premise that conveys sewage, rainwater, or other liquids wastes to a point of disposal.
Sewage pipe
Building sewer
Soil pipe
Drainage system
Lavatories shall have a minimum ____ inch water supply pipe.
1/4"
3/8"
5/8"
3/4"
Gas appliance connectors shall have an overall length not to exceed ____.
24"
36"
60"
72"
A water hammer arrester shall be used where ____ ____ valves are utilized.
Ball type
Inline gate
Spring check
Quick closing
A boiler completely filled with water, which furnishes hot water to be used externally to itself.
Potable supply boiler
Hot water boiler
Heating boiler
Hot water supply boiler
Pipes and pipe fittings, including valves and faucets, utilized in the water supply system shall have a maximum of ____% lead content.
1%
5%
7%
8%
All water service piping installed outside of the structure and underground shall have a minimum working pressure rating of ____ psi.
80 psi
100 psi
160 psi
180 psi
Attic passageways for electric water heaters shall not be less than 30 inches high and 22 inches wide and not more than ____ feet in length.
10'
20'
30'
40'
One way valve designed to allow air to enter the plumbing drainage system when negative pressures develop in the piping system.
Swing check
Studor-vent
Back pressure relief
Air admittance valve
Gas water heater vent connectors shall not be covered with ____.
Insulation
Drywall
Non-combustible materials
Duct tape
Waste outlets serving showers shall be at least ____ inches in diameter.
1.5"
2"
2.5"
3"
A piping arrangement in which a drain from a fixture, appliance, or device discharges directly into another fixture, receptacle or interceptor at a point below the flood level rim.
Air break
Indirect connection
Direct connection
Barometric relief
All indirect waste piping that exceeds 2 feet in developed length measured horizontally, or 4 feet in total developed length, shall be ____.
1.5" minimum size
Trapped
Run at 1/4" minimum pitch
Accessible
Any pipe or fitting that makes an angle of less than 45 degrees with the horizontal.
Vector piping
Horizontal piping
Drainage piping
Vent piping
2.5” or less horizontal drainage pipe shall slope a minimum of ____ inch per foot.
1/8"
1/4"
3/8"
1/2"
A type “B” or a type “L” vent used to vent a gas-fired water heater shall terminate at least ____ feet in vertical height above the highest connected equipment draft hood or flue collar.
2 feet
5 feet
10 feet
15 feet
The temperature of water from tankless water heaters shall be a maximum of ____ degrees F when intended for domestic use.
120 degrees C
86 degrees C
120 degrees F
140 degrees F
The size of the drainage piping shall not be ____ in size in the direction of the flow.
Increased
Reduced
Changed
None of the above
Installing waste piping at a slope greater than ½” per foot of run will insure proper drainage?
Yes
No
When no solids are introduced
When used as a roof drain only
Trough urinals shall be ____.
At least 8" x 8" x 8"
Fabricated of 20 gage stainless steel
Set at a minimum of 1/4" pitch per foot
Prohibited
A pressure spike in the water distribution system occurring during thermal expansion is caused by ____?
Transient surges in the water supply
A defective water heater thermostat
Check valve or backflow preventer in water service piping
Well pump pressure switch defects
Restaurants shall have a minimum of 1 lavatory for each ____ persons.
200
300
400
500
Air chambers absorb shock in water piping systems by compressing air during abrupt changes in flow rate – true or false:
True
False
The supply lines and fittings for every plumbing fixture shall be installed so as to prevent ____.
Leaks
Kinks
Back flow
Corrosion
Is acrylonitrile butadiene styrene pipe approved for above-ground storm drainage pipe?
Yes
No
Only in sizes 4" and larger
Only in sizes 3" and smaller
Plumbing fixtures shall be installed so as to afford easy access for ____ both the fixture and the area around the fixture.
Cleaning
Maintenance
Waterproofing
None of the above
Air that is provided to replace air being exhausted.
Exhaust air
Make-up air
Excess air
Combustion air
Joints for hub and spigot pipe shall be firmly packed with ____ or hemp.
Lead
Packing
Oakum
Vermiculite
Joint compound tape shall be applied on the ____ threads only.
Female threads
Defective threads
Male threads
All threads
Cleanouts with opening at a finished wall shall have the face of the opening located within ____ of the finished wall surface.
1 inch
1.5 inches
2 inches
2.5 inches
Whirlpool bathtub pumps shall be located ____ the weir of the fixture trap.
Next to
Below
Not near
Above
The static pressure applied at the base of a column of water is proportional to the height of the column of water.
True
False
Only if the column is 1" squared in area
None of the above
Water closet bowls for public or employee toilet facilities shall be of the ____ type.
Non-absorbent
Open-front
Elongated
Non-metallic
The principal pipe artery to which branches are connected.
Trunk line
Main
Building drain
Soil stack
When sizing a Natural Gas less than 2-pound semi-rigid copper fuel gas system with .5 IWC pressure drop and a specific gravity of 0.60, the maximum cubic feet per hour of gas flow allowed through a 5/8” ACR tube 70 feet in length is:
47
42
39
36
The maximum number of lavatories on a 2 ½” horizontal waste line is:
8
10
12
14
Hub and Spigot cast-iron piping in 10-foot lengths, installed horizontally, shall be supported at intervals not more than:
4
5
6
10
A water closet, lavatory, or bidet shall not be closer than ____ inches from its center to any side wall, partition, vanity, or other obstruction.
15"
18"
24"
30"
The minimum size vertical drain for a residential kitchen sink with a food waste grinder is:
1 1/4"
1 1/2"
2"
2 1/2"
A three-inch horizontal drainage pipe shall be run in practical alignment and at a uniform slope of not less than ____.
1/8"
1/4"
3/8"
1/2"
The vent for a kitchen sink serves as a drain for a laundry tray, the size of the wet vented section is:
1 1/2"
2"
2 1/2"
3"
What is the maximum developed length of a 1 ½” vent on a 2” waste stack carrying 20 DFU’s?
30'
40'
50'
55'
A pressure regulator and strainer is required when the local water pressure in excess of:
60 psi
70 psi
80 psi
100 psi
A secondary roof drainage system is permitted to discharge ____.
Above grade
To the parking areas
To the building sewer
Away from the footings
A vent connector on a gas water heater shall be installed with a minimum rise of:
1/8" per foot
1/4" per foot
3/8" per foot
1/2" per foot
The minimum size common vent for 5 lavatories at different levels is:
2"
2 1/2"
3"
4"
A valve that has the highest friction loss to water flow is the:
Gate valve
Outside screw and yoke
Balancing valve
Globe valve
What is the maximum DFU load a 4” wet vent can carry?
6
12
24
32
A backwater valve is used to:
Eliminate back pressure in the vent system
Reduces backflow from deptic tank connections
Prevents reverse flow in drainage systems
None of the above
Prohibited on combination waste and vent systems are:
Bathtubs
Showers
Urinals
Floor sinks
One of the following is not a standard fitting:
A wye
A 60-degree wye
1/8 bend
45-degree tee
A 6" horizontal storm drain pipe installed with a 2% slope will be adequate for what maximum size roof area with a 3" per hour rainfall rate?
7,133
10,066
13,700
30,650
Is schedule 80 galvanized steel pipe allowed by Code for underground drainage and vent piping?
Yes
Only in residential applications
No
Only in commercial applications
A Quorum for the North Carolina Building Code Counsel is:
5 members
7 members
9 members
11 members
Can the State Board suspend your license for charging excessive prices?
Yes
No
For service related calls only
Only in cases of unlicensed activity
When calculating indoor combustion air requirements for a water heater, how much combustion air does a 65,000 btu/hr water need for the space to be considered unconfined?
220 cubic feet of combustion air
2800 cubic feet of combustion air
3250 cubic feet of combustion air
3650 cubic feet of combustion air
ABS DWV pipe installed horizontally shall be supported at intervals not to exceed:
3'
4'
6'
8'
A 60 GPM sewage injector pump is connected to a drain line with a 40 DFU load already on the line. What is the new DFU load after connecting the ejector?
160 dfu
150 dfu
140 dfu
130 dfu
Indirect waste pipes shall be trapped when the total developed length exceeds:
24"
30"
54"
60"
{"name":"Plumbing Test", "url":"https://www.quiz-maker.com/QPREVIEW","txt":"To prevent the entry of rodents into the building, strainer plates on drain inlets shall be be installed so that the openings are not greater than ____ inches in the least diameter., A pipe sleeve used for pipe protection shall be ____ greater than the size of the pipe passing through the wall., Water service piping shall be installed not less than ____ below the finished grade.","img":"https://www.quiz-maker.com/3012/images/ogquiz.png"}
More Quizzes
The cost of living
1166
Clash of Clans Hack - Working Gold and Gems Hack for COC
100
What uniform ?
100
Do we need to expand the role of CARE or create a Parent/Child/Family support group within the UUCY
13611
Spanish Vocab Quiz- Friday 8/27
10528
David Domoney's Botany Quiz Part Two
840
Dik-dak-dawk
10526
Computer Networks - Networking Fundamentals
6318
Paws VS Stars
100
Test Quiz
320
Tri Harder
12623
Oh god, is it wednesday again?
30150